36 x OM3 Premises Distribution Low Smoke Zero Halogen Riser Indoor/Outdoor Cable


See all Indoor/Outdoor Riser LSZH Premises Distribution (ICRZ-I/O, PDRZ-I/O) products
Description
Standards
International : EN 50173; IEC 60332-1-2; IEC 60332-1-3; IEC 60332-2-2; IEC 60332-3-24 Cat.C; IEC 60332-3-25 Cat.D; IEC 60754-1; IEC 60754-2; IEC 61034-2; ISO/IEC 11801; NES 713National : ANSI/ICEA S-104-696; ANSI/ICEA S-83-596; ANSI/TIA-568.3-D; Telcordia GR-409
Description
Berk-Tek's tight buffered cable is available with standard multimode, single-mode and GIGAliteTM fibers.
Construction
900 µm buffered fibers surrounded by aramid yarns. Sheathed using a special, state-of-the-art low smoke zero halogen polymer material.
All dielectric.
Outdoor Considerations
- These black jacketed water-blocked riser-rated LSZH cables feature UV and fungus resistant jacketing.
- For use in conduit, below the frost line.
- Loose Tube cables are recommended if interbuilding conduit systems lie above the frost line and are likely to fill with water.
- Tight Buffer fiber cables are not suitible for aerial-lashed installations.
Flame Rating
Riser, Low-Smoke, OFNR - NFPA 130-2014 Compliant
Applications
Berk-Tek's tight buffered cable is intended for all high speed data applications including:
- ETHERNET: 10BASE – 400GBASE (10BASE, 100BASE, 1000BASE, 10GBASE, 40GBASE, 100GBASE, 400GBASE)
- Fibre Channel: 1G-FC – 128GFC (1, 2, 4, 8, 16, 32, 128 GFC)
- SONET: OC-1 – OC-768 (OC -1, 3, 12, 24, 48, 192, 768)
- SDH: STM-0 – STM-256 (STM-0, 1, 4, 16, 64, 256)
- OTN: OTU-1 – OTU4 (OTU1, 2, 2e, 2f, 3, 3e2, 4)
- CPRI: CPRI-1 – CPRI-9 (CPRI-1, 2, 3, 4, 5, 6, 7, 7a, 8, 9)
- PON (SMF): RFoG, APON, BPON, EPON, GPON, WDM-PON, NG-PON
Features
- Low Smoke Zero Halogen Riser-rated UV and fungus resistant polymer used for jacket and subunits
- Flexible, small diameter, 900 µm tight buffered construction
- High tensile strength and small diameter design
- Two to 48 count fiber construction riser-rated LSZH designs ideal for indoor/outdoor, horizontal and backbone installation
- Single-mode, multimode, and hybrid designs available
- Water blocked for Indoor/Outdoor installations, in-conduit and below the frost line.
Benefits
- Cost-saving design, easy to install and terminate
- Provides for greater pulling distances thus reducing installation time
- Assurance that cables will meet required specifications for communication networking applications
- Broad design selection allows for mix and match of fiber components to specific networking applications
Country of Origin: U.S.A.
Characteristics
Construction characteristics | |
---|---|
Fiber optic type | OM3 50/125 |
Type of cable | Tight Buffered (TB) |
Jacket Material | LSZH-FR |
Sheath colour | Black |
Dimensional characteristics | |
Number of optical fibres | 36 |
Cable diameter (Nominal) | 0.555in |
Nominal outer diameter | 14.1mm |
Nominal cable weight | 115lb/kft |
Approximate weight | 171kg/km |
Transmission characteristics | |
Optical performance | EB (50/125 GIGAlite-10, OM3) |
Attenuation, max. 850 nm (cabled) | 3.0dB/km |
Attenuation, max. 1300 nm (cabled) | 1.0dB/km |
Mechanical characteristics | |
Maximum installation tension | 300lb |
Maximum installation tension | 1335N |
Max. Load. Long Term (lbs) | 90.0lb |
Max. Load. Long Term | 400.0N |
Impacts per TIA/EIA FOTP-25 | 2 at 5.88 N-m |
Crush resistance per TIA/EIA FOTP-41 | 110N/cm |
Cable flexibility per TIA/EIA FOTP-104 | 25 cycles |
Usage characteristics | |
Minimum Bending Radius - Install | 8.3in |
Minimum Bend Radius - Install | 21.1cm |
Minimum Bending Radius - LongTerm | 5.6in |
Minimum Bending Radius - LongTerm | 14.1cm |
Recommended operating temperature range | -40 .. 75°C |
Ambient installation temperature, range | -20 .. 75°C |
Recommended storage temperature range | -40 .. 85°C |
Field of application | Indoor, Outdoor |
Docs and info
-
Standard Sheath Colors - Tight Buffer - Black
-
Manufacturing Release
IMPORTANT NOTICE: This product specification is provided for informational purposes only in order to illustrate typical product constructions, applications and/or methods of installation. Because conditions of actual installation and use are unique and will vary, Berk-Tek makes no representation or warranty as to the reliability, accuracy or completeness of this data, even if Berk-Tek is aware of the product's intended use or purpose. Furthermore, this data does not constitute, nor should it be regarded or relied upon, as professional engineering advice. Installation of product should only be done by qualified personnel and in conformance with all safety, electrical and other applicable codes, standards, rules or regulations. Appropriate and correct product selection, installation and use, and compliance with all such codes, standards, rules and regulations, is a customer/end-user responsibility. Product specifications, standards, programs or services are subject to improvement or changes without notice. Berk-Tek accepts no liability for typographical errors, technical inaccuracies, omissions or misuse of the information contained herein. Changes will be periodically made to address any such issues.